Device application Distribution Range of product Acti9 Range Acti9 Product name XC60 Product or component type Miniature circuit-breaker Device short name xC60 Poles description 1P Number of protected poles 1 [In] rated current 6-32A Network type DC
ACTrip unit technology Thermal-magnetic Curve code C Utilisation category Category A conforming to IS/IEC 60947-2 Suitability for isolation Yes conforming to IS/IEC 60947-2
Network frequency | 50/60 Hz |
---|---|
[Ue] rated operational voltage | 220...240 V AC 50/60 Hz 12...48 V DC 60 V DC |
Magnetic tripping limit | 8 x In +/- 20 % |
Breaking capacity | 10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2 |
[Ics] rated service breaking capacity | 15 kA conforming to IS/IEC 60947-2 - 12...48 V DC 6 kA conforming to IS/IEC 60947-2 - 60 V DC 7.5 kA conforming to IS/IEC 60947-2 - 220...240 V AC 50/60 Hz |
Limitation class | 3 conforming to IS/IEC 60947-2 |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IS/IEC 60947-2 |
[Uimp] rated impulse withstand voltage | 4 kV conforming to IS/IEC 60947-2 |
Contact position indicator | Yes |
Control type | Toggle |
Local signalling | ON/OFF indication |
Mounting mode | Clip-on |
Mounting support | 35 mm DIN rail |
Comb busbar and distribution block compatibility | Top: YES |
9 mm pitches | 2 |
Height | 85 mm |
Width | 18 mm |
Depth | 77.5 mm |
Net weight | 0.115 kg |
Colour | White |
Mechanical durability | 20000 cycles |
Electrical durability | 20000 cycles |
Connections - terminals | Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (top) |
Wire stripping length | 13 mm for top or bottom connection |
Tightening torque | 2 N.m |
Earth-leakage protection | Separate block |
Product compatibility | C60 auxiliary C60 accessories |
Overvoltage category | IV |
Standards | IS/IEC 60947-2 |
---|---|
IP degree of protection | IP20 |
Pollution degree | 3 |
Tropicalisation | 2 conforming to IEC 60068-1 |
Relative humidity | 95 % at 55 °C |
Ambient air temperature for operation | -30…70 °C |
Ambient air temperature for storage | -40…85 °C |