MCB 1POLE

    Category: MCB
  • Brand: Schneider
  • Minimum quantity: 1
  • Price: ₹ 140

Single pole breakers are designed to serve low-voltage circuits. These are the MCBs that you usually use to control specific electric lines – socket outlets or lighting systems – in your home.



Device applicationDistribution
Range of productActi9
RangeActi9
Product nameXC60
Product or component typeMiniature circuit-breaker
Device short namexC60
Poles description1P
Number of protected poles1
[In] rated current6-32A
Network typeDC
AC
Trip unit technologyThermal-magnetic
Curve codeC
Utilisation categoryCategory A conforming to IS/IEC 60947-2
Suitability for isolationYes conforming to IS/IEC 60947-2

Network frequency50/60 Hz
[Ue] rated operational voltage220...240 V AC 50/60 Hz
12...48 V DC
60 V DC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2
15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2
6 kA Icu at 60 V DC conforming to IS/IEC 60947-2
[Ics] rated service breaking capacity15 kA conforming to IS/IEC 60947-2 - 12...48 V DC
6 kA conforming to IS/IEC 60947-2 - 60 V DC
7.5 kA conforming to IS/IEC 60947-2 - 220...240 V AC 50/60 Hz
Limitation class3 conforming to IS/IEC 60947-2
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IS/IEC 60947-2
[Uimp] rated impulse withstand voltage4 kV conforming to IS/IEC 60947-2
Contact position indicatorYes
Control typeToggle
Local signallingON/OFF indication
Mounting modeClip-on
Mounting support35 mm DIN rail
Comb busbar and distribution block compatibilityTop: YES
9 mm pitches2
Height85 mm
Width18 mm
Depth77.5 mm
Net weight0.115 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability20000 cycles
Connections - terminalsTunnel type terminals (bottom) 16 mm² flexible
Tunnel type terminals (bottom) 25 mm² rigid
Biconnect (top)
Wire stripping length13 mm for top or bottom connection
Tightening torque2 N.m
Earth-leakage protectionSeparate block
Product compatibilityC60 auxiliary
C60 accessories
Overvoltage categoryIV

 

StandardsIS/IEC 60947-2
IP degree of protectionIP20
Pollution degree3
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Ambient air temperature for operation-30…70 °C
Ambient air temperature for storage-40…85 °C